Xi'an Kacise Optronics Co.,Ltd.

Kacise, understanding your automation needs.

Manufacturer from China
Verified Supplier
7 Years
Home / Products / Gas Detector Sensor /

SF6 Detection Accuracy ±2%FS KSF6-O2-202 Gas Detector for O2 Detection Range 0-25.0%vol

Contact Now
Xi'an Kacise Optronics Co.,Ltd.
Visit Website
Province/State:Shaanxi
Country/Region:china
Contact Person:MsEvelyn Wang
Contact Now

SF6 Detection Accuracy ±2%FS KSF6-O2-202 Gas Detector for O2 Detection Range 0-25.0%vol

Ask Latest Price
Video Channel
Model Number :KSF6-O2-202
Certification :CE
Place of Origin :CHINA
MOQ :1PCS
Payment Terms :L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability :1000 Piece/Pieces per Week negotiable
Delivery Time :5-8 work days
Packaging Details :each unit has individual box and all boxes are packed in standard packages or customers requests available
Detected Gas Types :SF6, O2
Detection Range :SF6: 0-1500ppm; O2: 0-25.0%vol
Resolution :SF6: 1ppm; O2: 0.1%vol
Detection Accuracy :SF6: ±2%FS; O2: ±0.5%vol
Alarm Error :SF6: ±5% (displayed value); O2: ±0.5%vol
Alarm Threshold :SF6: 1000ppm (adjustable); O2: 18%vol (adjustable)
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

KSF6-O2-202 Gas Detector

Product Introduction

The KSF6-O2-202 gas detector is a device that can monitor in real time the concentrations of sulfur hexafluoride (SF6) and oxygen in the air, as well as the environmental temperature and humidity in the working places of indoor electrical equipment. It gives early warnings according to the set alarm values. The instrument has a human body infrared monitoring function and can upload real-time detection data online through RS485 communication and WIFI communication functions. It is widely used in fields such as the gas analysis industry, industrial process control, environmental detection, and power plants and substations.

SF6 Detection Accuracy ±2%FS KSF6-O2-202 Gas Detector for O2 Detection Range 0-25.0%vol

Product Features

  • Non-dispersive infrared technology (NDIR) with independent intellectual property rights
  • Fast response time
  • Can ensure the accuracy error requirements across the entire temperature and humidity range
  • Automatic zero-point calibration function, automatically overcoming drift and false alarms
  • High reliability and long service life (>10 years)
  • Equipped with a PIR infrared monitoring function, supporting human body induction, and the induction range is not less than 3M
  • Capable of historical data recording and querying, automatic recording, automatic storage, and automatic updating of alarm events
  • Data uploading function
  • Small size, compact structure, and easy to install

Technical Parameters

Detected Gas Types SF6, O2
Detection Range SF6: 0-1500ppm; O2: 0-25.0%vol
Resolution SF6: 1ppm; O2: 0.1%vol
Detection Accuracy SF6: ±2%FS; O2: ±0.5%vol
Alarm Error SF6: ±5% (displayed value); O2: ±0.5%vol
Alarm Threshold SF6: 1000ppm (adjustable); O2: 18%vol (adjustable)
Response Time SF6: T90≤60s (diffusion type); O2: T90≤60s (diffusion type)
Temperature Detection Range -30℃ - +85℃
Temperature Detection Accuracy ±1℃ (full scale)
Humidity Range 0 - 99%RH
Humidity Accuracy ±5%RH
PIR Detection Distance ≧3m
Product Dimensions 20510558mm
Product Weight <1.5kg
Output Mode 1. RS485 communication; 2. WIFI communication; 3. RS232 communication (customizable)
Designed Service Life >10 years
IP Protection Rating IP54 (can be customized according to actual applications)
Product Standard DL/T 1555-2016; DL/T 639; JB/T 10893
Temperature and Humidity -20 - +50℃; 0 - 90%RH (non-condensing)
Atmospheric Pressure 86kPa - 106kPa
Power Supply Voltage AC220V±10% (50Hz±1%)
Rated Power <15W

Inquiry Cart 0