Xi'an Kacise Optronics Co.,Ltd.

Kacise, understanding your automation needs.

Manufacturer from China
Verified Supplier
7 Years
Home / Products / Gas Detector Sensor /

KAN123 Gas Alarm Controller Detect Gases and Conserve Energy with ≤ 10W Power Consumption

Contact Now
Xi'an Kacise Optronics Co.,Ltd.
Visit Website
Province/State:Shaanxi
Country/Region:china
Contact Person:MsEvelyn Wang
Contact Now

KAN123 Gas Alarm Controller Detect Gases and Conserve Energy with ≤ 10W Power Consumption

Ask Latest Price
Video Channel
Brand Name :KACISE
Model Number :KAN123
Certification :CE
Place of Origin :CHINA
MOQ :1PCS
Payment Terms :L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability :1000 Piece/Pieces per Week negotiable
Delivery Time :5-8 work days
Packaging Details :each unit has individual box and all boxes are packed in standard packages or customers requests available
Communication Distance :≤ 1000m (RVSP1.5mm²)
Operating Voltage :AC220V ± 15%/50HZ
Detected Gases and Bus Capacity :ABUS four - wire bus, T
Alarm Threshold and Alarm Method :High - limit alarmLow - limit alarmAudible and visual alarm
Power Consumption :≤ 10W (excluding detector)
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

KAN123 Gas Alarm Controller

Product Introduction

It can record 1000 pieces of historical gas alarm information, 1000 pieces of historical fault information, and 500 pieces of system operation information. It has an automatic screen - saver function. The backlight will automatically turn off if there is no operation on the screen within 3 minutes. The controller is flexibly applicable and has the function of switching between four - wire and two - wire systems, which can be compatible with both four - wire and two - wire detectors. The controller is equipped with a networking communication interface, enabling the access of RS485 modules, Ethernet, LORA, 4G and other modules.

KAN123 Gas Alarm Controller Detect Gases and Conserve Energy with ≤ 10W Power Consumption

Product Description

Communication Distance Operating Voltage Detected Gases and Bus Capacity Signal Transmission
≤ 1000m (RVSP1.5mm²) AC220V ± 15%/50HZ Combustible gases, toxic and hazardous gases
Configured with 8/16/32/64 points, expandable to 128 points
ABUS four - wire bus, TBUS two - wire bus (< 32 points), Three - wire system (branch line)
Alarm Threshold and Alarm Method Power Consumption Control Output Display Method
High - limit alarm
Low - limit alarm
Audible and visual alarm
≤ 10W (excluding detector) Three - way programmable linkage output (contact capacity 5A/DC24V or 5A/AC220V), Pulse output: breaks after 500mS 5.4 - inch 192×64 pixel dot - matrix liquid crystal LED backlit display screen, using Chinese and English + icon display
Under - voltage Alarm Point and Indication Error Working Environment Detection Unit Optional Accessories
165V ± 10V, ± 5%FS Temperature: 0°C - 40°C, Humidity: ≤ 93%RH %LEL, PPM, %VOL
mg/m³, °C, %RH
Backup battery: 2 pieces of DC12V/4.5AH storage batteries, ASD - MK5215 isolated RS485 converter
(Optional modules below) LORA, TCP/IP, WIFI, 4G (CAT1)

Inquiry Cart 0